Earthing and Bonding Explained: What They Are and Why They Matter
Last reviewed November 2026
Earthing connects the metal parts of electrical equipment to earth so that, if a fault occurs, current flows safely and the protective device switches off the circuit quickly. Bonding connects metal pipes and other conductive parts together and to the main earthing terminal, so that they stay at the same voltage and a person cannot receive a dangerous shock by touching two of them at once. Both are essential safety measures in BS 7671, and both should be checked by a qualified electrician during inspection and testing.
This guide explains each in plain terms and what to look out for.
What earthing does
In a modern installation, every circuit includes a protective conductor, often called the earth wire. It connects the metal casings of appliances and fittings back to the main earthing terminal near the consumer unit. If a live conductor touches the metal casing, current flows through the earth path. This makes the fuse, circuit breaker or RCD operate and disconnect the supply, ideally within a fraction of a second.
Without a good earth path, the metal casing could stay live, and anyone touching it could receive a shock.
Where the earth comes from
The main earthing terminal connects to an earth provided either by the electricity network or by an earth electrode at the property. The three common arrangements are TN-C-S (often called PME), TN-S and TT. Each has different requirements, and some uses, such as EV chargers, need special attention. Our EV charger earthing and PME guide explains why.
What protective bonding does
Bonding is different from earthing. It links metal parts that could introduce a different voltage into the building, such as incoming water and gas pipes, to the main earthing terminal. This is called main protective bonding. You will often see green and yellow cables clamped to pipes near the meters, with a label that says something like "Safety electrical connection, do not remove".
The purpose is to keep all these metal parts at the same voltage during a fault, so there is no dangerous difference between them.
Supplementary bonding
In the past, bathrooms usually had supplementary bonding linking pipes, radiators and metal fittings together. Under current BS 7671 rules, supplementary bonding in a bathroom may be omitted when certain conditions are met, including RCD protection for the circuits in the room and adequate main bonding. An electrician will decide whether it is needed. Our bathroom electrical zones guide covers bathrooms in more detail.
Earthing colours
Modern protective conductors are green and yellow. Very old installations may have bare earth wires or no earth on lighting circuits at all. Lighting circuits without an earth are a common finding in older homes and can be a reason to consider rewiring. Read our old wiring colours and types guide and signs your home needs rewiring for more.
Signs earthing or bonding may need attention
You cannot test earthing yourself, but these signs suggest it is worth asking an electrician:
- No visible green and yellow bonding cables at the gas or water pipes
- Bonding clamps that are loose, corroded or disconnected
- Plastic pipework replacing metal, with old bonding left hanging
- Metal light fittings on a circuit with no earth wire
- A tingle when touching an appliance, tap or radiator
- An old fuse box with no RCD protection
If you feel a tingle or shock from any metalwork, stop using the appliance or area and get it checked urgently. If someone is injured, call 999.
How earthing and bonding are tested
During an EICR or after new work, the electrician measures:
- Continuity of protective conductors and bonding
- Earth fault loop impedance, which shows whether protective devices will operate quickly enough
- External earth fault loop impedance, which checks the earth from the supply
- Earth electrode resistance on TT systems
They will also check the size and condition of the main earthing and bonding conductors. Missing or inadequate main bonding is often recorded with a code on an EICR. Our guide to EICR codes explains the codes.
Why this is not DIY work
Earthing and bonding are fundamental to the safety of the whole installation. Removing, moving or adding earth connections can create a serious risk. When plumbers replace pipes, they should make sure bonding is reinstated, and an electrician should check it. Changes to the main earthing arrangement are electrical work that should be carried out and tested by a qualified electrician.
Next steps
If you are unsure about your earthing and bonding, an EICR is the most complete way to check. You can find out more on our EICR page and our domestic electrical page. To arrange an inspection, contact us.
When work is notifiable
Some earthing and bonding work forms part of notifiable work under Part P in England, such as a new circuit or a consumer unit replacement. A registered electrician will deal with notification and provide the right certificate. Minor work to reinstate bonding may be recorded on a Minor Electrical Installation Works Certificate. Our Part P and electrical certificates guide explains the paperwork.
Earthing in commercial premises
The same principles apply in shops, offices and industrial units, but systems are often larger, with distribution boards, steelwork, cable trays and equipment that all need earthing and bonding. Regular inspection and testing, sometimes called fixed wire testing, keeps these checks up to date. See our fixed wire testing guide.
Frequently asked questions
What is the difference between earthing and bonding?
Earthing gives fault current a safe path so protective devices switch off. Bonding links metal pipes and parts together so they stay at the same voltage during a fault.
What are the green and yellow cables on my pipes?
They are main protective bonding conductors. They connect incoming metal services to the main earthing terminal and should not be removed.
Do bathrooms still need supplementary bonding?
Not always. BS 7671 allows it to be omitted when certain conditions are met, including RCD protection and adequate main bonding. An electrician will decide.
I felt a tingle from a tap. What should I do?
Stop using the area or appliance and get it checked by a qualified electrician urgently. If someone is injured, call 999.
How is earthing tested?
An electrician tests protective conductor continuity, earth fault loop impedance and, on TT systems, earth electrode resistance, usually as part of an EICR.
Sources
- IET, BS 7671 Wiring Regulationshttps://electrical.theiet.org/bs-7671/
- Electrical Safety Firsthttps://www.electricalsafetyfirst.org.uk/
- GOV.UK, Approved Document P: electrical safety (dwellings)https://www.gov.uk/government/publications/electrical-safety-approved-document-p